TN/VAT Series

CENTRIFUGAL ROOF FANS WITH HORIZONTAL OUTLET

Applus

These centrifugal roof fans are designed to extract air and smoke in case of fire according to the international standard EN 12101 – 3:2002. Air flow discharge is vertical and the maximum intake air temperature is 80 [°C] in case of continuous service, or 400 [°C] for two hours only in case of fire.
Air flow rate ranges from a minimum of 500 [m3/h] to a maximum of 18000 [m3/h].

Documents

General catalogue product pages.

MANUFACTURING AND TECHNICAL FEATURES

Each model includes a base, uprights, a motor support plate, a protection guard and a radial wheel with galvanized steel backward blades, an air conveyor made of thermoplastic polymer (ABS) and a cased electric motor (IP 55, class “F” insulation) with external cooling fan. All parts are made of galvanized steel sheets except where otherwise noted.
Supported electric motors: single speed three phase motor voltage 230/400 [V] 50 [Hz], a double speed three-phase motor voltage 400 [V] 50 [Hz] or a single-phase motor voltage 230 [V] 50 [Hz].

OPTIONAL FEATURES

Electric motors supporting different voltage and frequency.

DATASHEETS

Key
— Power [kW]
— Static pressure [Pa]

4 POLES


 

6 POLES



 

8 POLES



 

Double speed

ACCESSORIES

Documents

 

Summary table

Frame adapter for silencers and gravity shutters frame adapters for circular ducts
Gravity shutter gravity shutter
Backplate for concrete backplate for concrete
Rising frame for flat surfaces (“purling box”) Purlingbox
Speed controllers Analog single phaseTrifase inverterThree phase change-over switchThree phase control board
Rotary isolator switch. Rotary isolator switch

WEIGHT AND DIMENSIONS

TN/VAT dimensions

Taglia/SizeAxA
[mm]
BxB
[mm]
C
[mm]
DxD
[mm]
∅E
[mm]
H
[mm]
[kg]
204005954035025050025
305608004046030064033
405608004046035064040
5071010004061040070052
6071010004061045074061
7090012604080050078073
8090012604580055082095
90900126045800600870116
100900126045800600940132